Schneider Electric, Altivar, PlantStruxure, Foxboro, and Life Is On Schneider Electric are trademarks and the property of Schneider Electric SE, its subsidiaries and affiliated companies. All other trademarks are the property of their respective owners. 98USB Solutions for every stage of your equipment’s life cycle At Schneider. Schneider Electric Manufacturing Bourguebus is ultimately consolidated by Schneider Electric Se. Relationship Start Node Node I D. Schneider Electric Leveraged To Multiple Secular Growth Drivers Nov. 18, 2020 4:24 AM ET Schneider Electric S.E. (SBGSY) ABB, AVVYY, EMR. 4 Comments 11 Likes Stephen Simpson.

Interface Description

IGSS offers an interface for the Modicon PLC series and Modbus compatible systems using the Serial Modbus RTU and ASCII protocols.
The communication driver uses standard RS-232 serial ports to connect to up to 8 PLCs. Each of these PLCs may in turn be connected to other devices (e.g. other PLCs) via a separate network (e.g. Modbus or Modbus Plus networks)
The communication interface supports both direct and dial-up connections.
The IGSS system polls the PLC equipment cyclically according to one of four user-defined time intervals. The time intervals are configurable from 100 milliseconds to 999 seconds. The system automatically groups process data in data blocks – thus fully exploiting the communication link in relation to the present configuration.

Technical Data

Schneider electric bourguebus driver manual

Schneider Electric Bourguebus Driver Updater

Bourguebus

Schneider Electric Bourguebus Driver Download

Electrical Interface:RS-232 point-to-point connection
Protocol:Modbus RTU/ASCII
Types of data:String, Fixed point 8, 16, 32, BCD 16, 32, Floating Point etc.
PLC types supported:All PLCs supporting AEG Modicon Modbus RTU/ASCII protocol. E.g. Milltronics Enviroranger ERS 500, GRUNDFOS CU401 Controller
Addressing:Node (PLC), data type (Coils, Discrete Input, Word Inputs, and Holding Registers), offset , bit offset (a whole number of words is read or written)
Supported platforms:Windows Vista, Windows XP, Windows 2003 Server, Windows 2000
Max. telegram size:Up to 250 bytes per telegram
Transmission speed:Up to 115 Kbaud depending on the PLC port speed
Throughput:3-4 telegrams per PLC per second (depending on baudrate)
Max. number of channels:Up to 8 connections are supported concurrently
PC hardware requirements:1-8 standard serial ports (COM ports). Standard modem(s) if dialled-up connections are used
PC software requirements:None